Installation guide, User Manual. APC Symmetra LX 16kVA Scalable to 16kVA N+1 Ext. Run Tower, 220/230/240V or Includes: CD with software, Documentation CD, User Manual, Web/SNMP. APC Symmetra LX 16kVA UPS instruction manual APC Symmetra LX Eaton 9170+ user manual APC SMX1000I + Service Bundle 3 operating instruction. Symmetra LX Rack-mount UPS Symmetra LX Tower UPS ® 990-1539B-001, 04/2006 Important Safety and Installation Instructions This manual provides instructions on the wiring and connections for the Symmetra LX tower and rack-mount UPS. All electrical power and power control wiring must be.
SYA12K16P - APC Symmetra LX 12kVA scalable to 16kVA N+1 Tower. User Manual, Web/SNMP Management Card. Standard Lead Time: Usually in Stock. SYA12K16RMP - APC Symmetra LX 12kVA Scalable to 16kVA N+1 Rack-mount, 208/240V Input, 208/240V and 120V Output. SYA16K16P - APC Symmetra LX 16kVA Scalable to 16kVA N+1 Tower, 208/240V Input, 208/240V and 120V Output. SYA16K16PXR - APC Symmetra LX 16kVA Scalable to 16kVA N+1 Ext. Run Tower, 208/240V Input, 208/240Vand 120V Output.
3-16kVA Service Bypass Panels
©2009 APC by Schneider Electric, APC, the APC logo, and Smart-UPS are owned by Schneider Electric industries S.A.S American Power Conversion Corporation, or their affiliated companies. All other trademarks are property of their respective owners.
990-1530B
Note: Read the safety information sheet before installation.
Illustrations in this document may differ slightly from the actual hardware.
Attention: This product is for use in a controlled environment. Refer to product specifications for environmental limits.
RACK MOUNTING
n
x4
x8
x2
oSet SBP in the rack. If hardwiring is required, see Connecting Power section before screwing into the rack.
x4
WALL MOUNTING
n
x8
oWhenever possible, attach one top screw and one bottom screw into a wall stud. If stud mounting is not possible, use an expandable wall anchor. Screws are not included; .25” x 2” lag bolts are recommended.
x4
TOWER OPTION (FOR SMART-UPS RT SETUPS ONLY)
n Remove screw from the top and bottom rear of both the UPS and SBP. Install tie brackets and reattach screws.
Front | Rear |
x4
x2
oUnscrew and remove top cover of the pAttach bracket to top of UPS and SBP. UPS.
x2
x1
qReattach top cover of the UPS.
Note: The SBP5000RMI2U, when used in conjunction with an SURT3000XLI or SURT5000XLI UPS in a tower configuration without an external battery pack (SURT192XLBP), is suitable for mounting on concrete or other non-combustible smooth surfaces only.
USER CONFIGURABLE
Attention: When using an online UPS, put the UPS in automatic bypass mode before rotating the SBP switch.
1.Normal: Power is directed from the utility outlet, through the Bypass Panel and UPS, and to connected equipment. For use during normal UPS operation.
2.Test: Power supplied to the UPS is not output. Use when tests are being conducted on the UPS, and connected equipment is not yet desired.
3.Bypass: Power from the utility outlet is filtered through the Bypass Panel, and to the connected equipment. Use to bypass the UPS, when functioning improperly.
Note: While operating in ‘Test’ or ‘Bypass’ mode, power to the connected equipment is not conditioned by the UPS. At this time, the “Equipment Protection Policy” is not valid.
IDENTIFYING THE PANEL
Service Bypass Panels will differ. Refer to chart for unit specifications. Note: HW= Hardwire
Service Bypass | Corresponding | Bypass | UPS | UPS | PDU |
Panel | UPS Systems | Input | Input | Output | Panel |
SBP3000RM2U | 100-120V Smart-UPS | L5-30P | L5-30R | L5-30P | (2) 5-20R, |
3kVA | (6) 5-15R |
SBP5000RMT2U | 200/208/240V | L6-30P | L6-30R | L6-30P | (2) L6-20R, |
Smart-UPS 3-4.5kVA | (2) L6-30R | ||||
SBP5000RMI2U* | 230V Smart-UPS | C20/HW | C19/HW | C20/HW | (2) C19, |
3-5kVA | (8) C13 |
SBP6KRMT2U** | 200/208/240V | L6-30P/ | L6-30R/ | L6-30P/ | (1) L6-20R, | |
Symmetra 2-6kVA | HW | HW | HW | (2) L6-30R | ||
SBP6KRMI2U | 230V Symmetra | HW | HW | HW | (4) C19 | |
2-6kVA | ||||||
SBP3000 | 100-240V Smart-UPS | HW | HW | HW | HW | |
3-5kVA with 30A HW | ||||||
input/output | ||||||
available | ||||||
SBP10KRMT4U | 200/208/240V | HW | HW | HW | (3) L6-20R, | |
Smart-UPS RT | (3) L6-30R | |||||
7.5-10kVA | ||||||
SBP10KRMI4U | 230V Smart-UPS RT | HW (3Ph | HW (3Ph | HW | (8) C13, | |
7.5-10kVA | or 1Ph) | or 1Ph) | (2) C19 | |||
SBP16KP | 200-240V | HW (3Ph | HW (3Ph | HW | HW | |
Symmetra LX | or 1Ph) | or 1Ph) | ||||
4-16kVA | ||||||
SBP16KRMI4U | 220-240V | HW (3Ph | HW (3Ph | HW | (3) 30A HW | |
Symmetra LX | or 1Ph) | or 1Ph) | ||||
4-16kVA | ||||||
SBP16KRMP4U | 200/208/240 | HW | HW | HW | (6) L14-30R | |
Symmetra LX | ||||||
4-16kVA | ||||||
SBP16KRMP4U-HW | 200/208/240 | HW | HW | HW | (1) L14-30R, | |
Symmetra LX | (3) L5-20R, | |||||
4-16kVA | (1) 100A HW |
*For loads exceeding 3kVA, hardwiring is necessary.
**For loads exceeding 5kVA, hardwiring is necessary.
CONNECTING POWER
Warning: Do not modify inlets or outlets. The SBP and UPS plugs and receptacles should match. For more information, contact APC.
1.Non-Hardwired Panels
1.Plug SBP UPS output cord into UPS PDU panel.*
2.Plug UPS input cord to SBP UPS input receptacle.*
3.Plug customer equipment into SBP PDU panel.
4.Plug SBP into utility power outlet.
*Units with IEC receptacles: Use jumper cables.
2. Hardwired Panels
Attention: Wiring must be performed by a qualified electrician.
1.Switch input circuit breaker off.
2.SBP units that will be rack-mounted: Set SBP in the rack.
3.Unscrew and remove top access panel.
4.If using SBP5000RMI2U or SBP6KRMT2U with a hardwired UPS: Unscrew existing terminal block wiring. Do not touch factory wiring (see E).
5.If using SBP5000RMI2U or SBP6KRMT2U with a hardwired UPS: Unscrew and remove rear input/output panel.
6.Remove circular knockouts from hardwiring input/output panel (see A, B, C, D: UO= UPS Output; UI= UPS Input; AI= AC Input; LD= Load).
SBP3000 units: Also, remove PDU output panel knockout plate.
SBP16KP units: Also, remove circular knockouts from PDU output panel.
7.Connect wires to terminal blocks (see E, F, G, H, I). Adhere to all national and local electrical codes.
8.Reinstall access panel.
9.Install hardwiring input/output panel.
10.SBP units that will be rack-mounted: Screw SBP into the rack.
A. | B. | C. | D. |
E. 2U PANELS
F. SBP10KRMT4U
G. SBP16KRMP4U, SB16KRMP4U-HW
H. SBP16KP
I. SBP10KRMI4U, SBP16KRMI4U
TROUBLESHOOTING
Use the chart below to solve minor SBP installation problems. Also, refer to the UPS User Manual Troubleshooting section. For more complex issues, refer to www.apc.com.
Problem and | Solution | |
Possible Cause | ||
UPS WILL NOT TURN ON AFTER ON BUTTON IS PUSHED | ||
SBP handle is in ‘Bypass’ position. | Rotate the SBP handle to the ‘Normal’ position. | |
There is no power at UPS input. | Check that the power cables from the SBP to the utility power, and | |
from the SBP to the UPS Input are securely connected. | ||
UPS is faulty or damaged. | Rotate the SBP handle into the ‘Test’ position. If the connected | |
equipment becomes energized, the UPS may be faulty. To confirm | ||
this, refer to UPS User Manual Troubleshooting. User ManualsUser Manuals are available to download free of charge from the Canon UK website. Canon instruction manual download. | ||
There is no power at the utility | Rotate the SBP handle into the ‘Test’ position. If the connected | |
power outlet. | equipment fails to become energized, the utility power outlet may be | |
faulty. Check the utility power supply by plugging a table lamp into | ||
the suspect outlet. If the utility outlet fails to power the lamp, contact | ||
qualified service personnel to restore power. | ||
UPS IS ONLINE; NOT POWERING ALL CONNECTED EQUIPMENT | ||
SBP output circuit breaker tripped. | Reduce the load by unplugging equipment. Reset the breaker. | |
There is no power at SBP output. | Check that the power cable from the SBP to the UPS output is | |
securely connected. |